Prestige TriMax Boiler
Manual Addendum
SECTION V - Installing Vent / Com-
bustion Air & Condensate Drain
Installing Vent and Combustion Air
The PRESTIGE must be vented and sup-
plied with combustion air as shown in the
PRESTIGE Vent Supplement, included in
the boiler installation envelope. Refer to
optional vent kit instructions for additional
vent installation instructions. Once instal-
lation is completed, inspect the vent and
combustion air system thoroughly to en-
sure systems are airtight and comply with
the instructions given in the venting sup-
plement and are within all requirements of
applicable codes. Failure to comply with
the installation requirements on the vent-
ing and combustion air piping will cause
severe personal injury or death.
Installing Condensate Drain Assembly
1. Locate the condensate drain assembly and
install as shown in Fig. 14.
2. A metal washer must be installed when in-
stalling the condensate drain assembly. On
all models except the Solo 399, the metal
washer must first be cut using a pair of di-
agonal cutting pliers to make it into a split
washer. Insert the metal washer into the re-
taining nut and screw onto the condensate
drain assembly without rubber gaskets. Use
the condensate drain assembly as a tool to
press the retaining nut with metal washer
onto the polypropylene condensate pan. Un-
screw the condensate drain assembly and
proceed to the next step.
Ensure installation of the condensate drain
assembly included the metal washer. Fail-
ure to comply could result in the trap as-
sembly dislocating from the boiler.
The installer may want to fill the conden-
sate trap with water prior to assembling
on the unit.
3. Slide the rubber seals from the condensate
drain assembly over the heat exchanger con-
densate drain nipple. Connect the condensate
drain assembly to the retaining nut and tighten.
Ensure the condensate drain assembly
contains the plastic seated ball. Do not in-
stall the condensate drain assembly if the
ball is lost or missing, replace the entire
assembly.
4. Remove the compression nut and rubber
seal from the drain outlet.
5. Using 3/4” x 2 flexible PVC tube provided,
slide the compression nut and rubber seal
over the pipe
The use of 3/4” PVC or CPVC pipe is also
acceptable. If 3/4” pipe is used deburr
and chamfer pipe to allow mating onto
the drain assembly.
6. Thread the rubber seal into the compression
nut to ease installation of the pipe to the
drain assembly.
7. Seat the pipe onto the drain assembly and
tighten the compression nut. Hand tight
only!
The installer may opt to using 13/16" ID
tubing in lieu of rigid piping.
NOTICE
DANGER
WARNING
NOTICE
WARNING
NOTICE
This addendum replaces Section V in the Prestige Installation and Maintenance
Manual
Vue de la page 0
1 2

Résumé du contenu

Page 1 - Manual Addendum

1Prestige TriMax Boiler Manual AddendumSECTION V - Installing Vent / Com-bustion Air & Condensate DrainInstalling Vent and Combustion AirThe PREST

Page 2 - Date: 7/25/2013

2Prestige TriMax Boiler Manual AddendumThe drain line materials must be an ap-proved material by the authority havingjurisdiction. In absence of such