Warranty Registration Card must be filled out by the customer and mailed within thirty (30) days of installa-
tion in order to gain warranty coverage.
When receiving the PRESTIGE Solo unit, any claims for damage or shortage in shipment must be filed
immediately against the transportation company by the consignee.
Leave all documentation received with appliance with owner for future reference.
* I N S T A L L A T I O N A N D M A I N T E N A N C E *
* I N S T A L L A T I O N A N D M A I N T E N A N C E *
M A N U A L
M A N U A L
2010-7 Manual Prestige Solo 60/175/250/399 - Revised 02/17/10
If the information in this manual is not followed exactly, a fire or explosion may
result causing property damage, personal injury or death.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of
this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance
- Do not touch any electrical switch; do not use any phone in your building.
- Immediately call your gas supplier from a neighbor’s phone. Follow the gas
supplier’s instructions.
- If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the
gas supplier.
prestige
Solo 60
Solo 175
Solo 250
Solo 399
Water Boiler
Series III
L
I
S
T
E
D
WARNING
NOTICE
Vue de la page 0
1 2 3 4 5 6 ... 87 88

Résumé du contenu

Page 1 - Water Boiler

Warranty Registration Card must be filled out by the customer and mailed within thirty (30) days of installa-tion in order to gain warranty coverage.W

Page 2 - Table of Contents

Pre-Installation Items- Reference the appropriate vent supple-ment for clearance requirements.To provide serviceability to the unit it isrecommended

Page 3

Combustion Air Venting5SECTION II - Combustion Air andVentingCombustion Air ContaminationIf the PRESTIGE Solo combustion airinlet is located in

Page 4

6Combustion Air VentingVentilation and Combustion AirRequirements - Direct VentA Direct Vent appliance utilizes uncontaminedoutdoor air (piped directl

Page 5

7Combustion Air VentingMethods of Accessing Combustion Air Into ASpace - Category IVIndoor Combustion AirThe methods listed in this section fora

Page 6

8Combustion Air Venting- Not less than the sum of the areas of allvent connectors in the space.Two Permanent Openings Method. Two permanent openings

Page 7

9Combustion Air VentingOutdoor Opening(s) Location. Outdoor open-ing(s) shall be located in accordance with theOutdoor Combustion Air section.Outd

Page 8

10Combustion Air VentingRemoval of an Existing Boiler from aCommon Vent SystemWhen an existing boiler is removed from acommon venting sys

Page 9 - Pre-Installation Items

11Combustion Air VentingFor direct-vent appliances, mechanical-vent heating appliances or domestic hotwater equipment, where the bottom of the

Page 10 - BEST PRACTICE

12Unit PreparationsSECTION III - Unit PreparationsHandling InstructionsThe PRESTIGE Solo is generally easier tohandle and maneuver once re

Page 11 - Combustion Air Venting

13Unit PreparationsPRESTIGE Solo 60/175/250 Stud Walls -Installation 1. Locate the studs in the general area of theboiler placement.2. Place the w

Page 12

Table of ContentsiPRODUCT AND SAFETY INFORMATIONDefinitions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 13 - Fig. 1:

Boiler PipingSECTION IV - Boiler PipingGeneral Piping Requirements- All plumbing must meet or exceed all local,state and national plumbing codes.- Su

Page 14 - Fig. 4:

15Boiler PipingBoiler Return Connectionwith Tee Fitting andBoiler Drain ValveBoiler Supply Connection Pressure Relief Valve(Supplied with Boile

Page 15

Boiler PipingAdditional Limit ControlIf a separate LWCO device is required by cer-tain local jurisdictions or when the boiler isinstalled above

Page 16

Boiler PipingThe expansion tank must be located as shownin Fig. 6 and Fig. 7 on page 18 when using aprimary/secondary piping arrangement or asper

Page 17

18Boiler PipingMax.12" BoilerSupplySystemReturnSystemColdWater FillBoilerSupplyReturn71012354666111271109843666ColdWater FillBoilerSupplyMinimum3

Page 18 - Unit Preparations

19Boiler PipingSystem Piping - Zone ValvesConnect the PRESTIGE Solo to the system pip-ing as shown in Fig. 10 page 21 when zoningwith zone valves.

Page 19

20Boiler Piping1. PRESTIGE Solo boiler2. SMART water heater3. Isolation valve4. DHW circulator 5. CH circulator 6. Flow/check valve7. Pressure rel

Page 20 - SECTION IV - Boiler Piping

21Boiler Piping5 5 4 6 1 2 3 3 3 3 3 9 8 10 11 4 4 4 4 4 4 Zone Load Additional 7 6 Max. 12" Zone Load 2655461312981011444444Zone Load 7Additi

Page 21 - Boiler Piping

22Boiler Piping1 2 7 6 4 Additional Zone Load 4 5 4 4 4 2 Zone Load 9 8 10 11 4 5 12 P 1 2 7 6 4 2 Single Zone load 9 8 10 11 4 3 Fig. 11: CH Syste

Page 22

23Boiler Piping2 5 5 4 6 1 3 13 12 9 8 10 11 4 4 4 Radiant Zone Additional 4 4 4 6 7 Radiant Zone Max. 12" Note: Manifold mounted valveactuat

Page 23

Table of ContentsiiBoiler System Piping Applications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Expansion Tank and Makeup Water

Page 24

24Boiler Piping3 2 2 2 2 To the System 5 5 5 1 1 1 From the System 4 6 7 8 9 2 12" Max. 3 2 3 2 5 5 5 1. Boiler circulator2. Isolation valve3.

Page 25 - EST PRACTICE

25Installating Vent/Combustion Air & Condensate DrainSECTION V - Installing Vent /Combustion Air & Condensate DrainInstalling Vent and Combust

Page 26

26Installating Vent/Combustion Air & Condensate DrainWhen selecting and installing a conden-sate pump, ensure the pump is approvedfor use with con

Page 27

27Gas PipingSECTION VI - Gas PipingGas Supply Piping ConnectionThe gas supply piping must be installedin accordance to all applicable local,state

Page 28

28Gas PipingNATURAL GASPipe Sizing - Natural GasRefer to Table 1 for schedule 40 metallic pipelength and diameter requirements for naturalgas, b

Page 29

29Gas PipingPROPANE GASPipe Sizing - Propane GasContact the local propane gas supplier for rec-ommended sizing of piping, tanks and 100%lockup g

Page 30

30Gas PipingGas ValveOrifice GasketsVenturiFig. 18: Gas Valve / Venturi Assembly - PRESTIGE Solo 399VenturiInlet SupplyPressure PortPropaneOrificeGas

Page 31 - SECTION V - Installing Vent /

31Internal WiringSECTION VII - Internal WiringELECTRICAL SHOCK HAZARD. Foryour safety, disconnect electrical powersupply to the unit before

Page 32

32Internal WiringO-10v External Inputs (+)DHW Sensor or ThermostatDHW Sensor or ThermostatO-10v External Inputs (-)Gas ValvePRESTIGE Solo 399 OnlyHeat

Page 33 - Gas Piping

33External WiringSECTION VIII- External WiringInstallation ComplianceAll field wiring made during installation mustcomply with:- National Electrical C

Page 34

iiiTable of ContentsDomestic Hot Water Aquastat Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33Thermostat Wiring . . . . . . . . .

Page 35

34External Wiring24 VTransformerby OthersHoneywell V8043Zone Valvesor EquivalentHoneywell R8285DTransformer / Relayor Equivalent 24V Terminal StripSys

Page 36

35External WiringHNHigh Voltage120V. A . C .24V. A . C .RoomThermostatRoomThermostatZone 1Zone 2Additional zonesAdditional zones maybe added as shown

Page 37 - SECTION VII - Internal Wiring

36External WiringTTTo Prestige 24V Terminal StripCirculatorZone 1Thermostatzone 1HoneywellR845ARelay120HVA CNCirculatorZone 2Thermostatzone 2Additiona

Page 38 - Internal Wiring

37Start-Up PreparationSECTION IX - Start-Up PreparationCheck Boiler System Water ChemistryDo not use petroleum-base cleaning orsealing compounds

Page 39 - SECTION VIII- External Wiring

38Start-Up PreparationUse of Antifreeze in the Boiler SystemNEVER use automotive or ethylene gly-col antifreeze or undiluted antifreeze inthe primary

Page 40 - External Wiring

39Start-Up PreparationCheck For Gas LeaksPrior to start-up and during initial opera-tion, smell near the floor and around theunit for gas odorant or a

Page 41 - 3 Wire Zone Valve

40Start-Up ProceduresSECTION - Start-Up ProceduresFinal Checks Before Start-Upc Read page 45 through 48 regarding theoperation of the PRESTIGE

Page 42

41Start-Up Proceduresc Check Vent Piping and Combustion AirPiping.Check for gas-tight seal at every con-nection and seam of the ventin

Page 43 - Start-Up Preparation

42Start-Up ProceduresWARNINGFOR YOUR SAFETY READ BEFORE LIGHTINGOPERATING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCE1. STOP! Read the safety informati

Page 44

43Start-Up Procedures5. Calculate Natural gas input using the fol-lowing equation:3600 x 1000 / number of second recordedfor one cubic foot of g

Page 45

ivTable of ContentsSECTION XI - OUTDOOR RESET CONTROLMounting the Outdoor Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 46 - Start-Up Procedures

44Start-Up Proceduresapproximately 1 minute. After this timeperiod, the control module will begin tomodulate the burner firing rate ba

Page 47

45Start-Up ProceduresBoiler Control DisplayStandby Mode This is the standard mode for the PRESTIGESolo. The control automatically returns to thismo

Page 48

46Start-Up ProceduresSTANDBY, no demand for heatFan prepurge or post purge cycleIgnition sequenceBurner ON for space heating (CH)Burner ON for domesti

Page 49

47Start-Up ProceduresSetting The Boiler ParametersParameter mode To access PARAMETER mode when the sys-tem is in STANDBY mode, press the MODEbut

Page 50

48Start-Up ProceduresAccessing Boiler Information Information mode To switch from STANDBY mode to INFOR-MATION mode, press MODE twice.Press STE

Page 51

49Start-Up ProceduresError (Hard Lockout) ModeIf a serious fault occurs, the system enters ahard lockout condition which requires a manu-al re

Page 52

50Outdoor Reset ControlSECTION XI - Outdoor Reset ControlThe boiler setpoint for a heating call can befixed or vary with the outdoor temperatu

Page 53

51Outdoor Reset ControlSummer / Winter Switch at BoilerIf required the CH (Central Heating) system canbe turned off at the boiler, similar to a manual

Page 54

52Outdoor Reset ControlCH Reset Curve Warmest Day(Parameter 12)This parameter is not applicable if an outdoorsensor is not connected to the boiler. W

Page 55

53Outdoor Reset ControlGraph 1 illustrates Parameter 4 adjusted to 140ºF target temperature at 0ºF outdoorair temperatureTable 3: Outdoor Air Temperat

Page 56 - Outdoor Reset Control

vTable of ContentsInspect Vent and Combustion Air Piping . . . . . . . . . . . . . . . . . . . . . 60Check Boiler System . . . . . . . . . . . . . . .

Page 57

54External Modulating ControlSECTION XII - External ModulatingControlThe boiler can directly accept an analog 0-10VDC signal to control the firi

Page 58

55External Modulating ControlFactory Setting Parameters1 140ºFDHW Setting2 01 DHW Application Selection3 01 CH Application Selection4 186ºF CH Maximum

Page 59

56Check-Out ProceduresSECTION XIII- Check-Out ProceduresPerform the following check-out proce-dures as outlined and check off items ascompleted. W

Page 60 - External Modulating Control

57Installation RecordSECTION XIV - Installation Record

Page 61

58Maintenance ScheduleSECTION XV - Maintenance ScheduleService TechnicianAt least on an annual basis the following main-tenance should be performed by

Page 62 - Check-Out Procedures

59Maintenance ProceduresSECTION XVI - MaintenanceProceduresMaintenance ProceduresThe PRESTIGE Solo should be inspect-ed and serviced annually, pr

Page 63 - Installation Record

60Maintenance ProceduresClean Condensate Drain Assembly1. Loosen the retaining nut from the conden-sate drain assembly and disconnect theassemb

Page 64 - Maintenance Schedule

61Maintenance ProceduresCheck Expansion TankRefer to Section IV - Boiler Piping for rec-ommended location of the expansion tankand air el

Page 65 - Procedures

62Maintenance ProceduresCheck Control WiringInspect all control wiring. Ensure wiring is ingood condition and properly connected.Check Control Set

Page 66 - Maintenance Procedures

63Maintenance ProceduresCheck Flame SignalThe flame signal can be read from item E of theinformation mode. It should be a min. 3μ Α −DC.Check the igni

Page 67

Product & Safety Information1Indicates the presence of a hazardoussituation which, if ignored, will result indeath, serious injury or sub

Page 68

64Maintenance ProceduresThe combustion chamber insulationcontains ceramic fibers, which are clas-sified as a possible human carcinogen.When e

Page 69

65Replacement Parts598135267Fig. 26: PRESTIGE Solo Jacket ComponentsItemPart #PRESTIGESolo 60Part #PRESTIGESolo 175-250Part #PRESTIGESolo 399Descripti

Page 70

66Replacement Parts8592344671Fig. 27: PRESTIGE Solo 60 Internal ComponentsItem Part # Description1 PSRKIT01 Heat Exchanger Body2 PSRKIT02 Vent Outlet

Page 71 - Replacement Parts

67Replacement Parts854410971326Fig. 27A: PRESTIGE Solo 175/250 Internal ComponentsItemPart #PRESTIGESolo 175/250Description1PSRKIT25 Heat Exchanger Bo

Page 72

68Replacement Parts871012344569Fig. 27B: PRESTIGE Solo 399 Internal ComponentsItemPart #PRESTIGESolo 399Description1 PSRKIT44 Heat Exchanger Body 2 PS

Page 73

69524813967Fig. 28: PRESTIGE Solo 60/175/250 Burner ComponentsReplacement PartsItemPart #PRESTIGESolo 60Part #PRESTIGESolo 175-250Description1 PSRKIT0

Page 74

70Replacement Parts769121012134358Fig. 28A: PRESTIGE Solo 399 Burner ComponentsItemPart #PRESTIGE Solo 399Description1 PSRKIT37 Combustion Chamber Ins

Page 75

713Fig. 29: PRESTIGE Solo Electronic ComponentsReplacement PartsItem Part # Description1 PSRKIT50 Prestige Control Module2 PSRKIT19 Transformer with S

Page 76

72Product Specifications35.50” [902 mm]15.43” [392 mm]9.87” [251 mm]9.87” [251 mm]2.2” [56 mm]3” [76 mm]1 ” NPT Boiler Supply1/2” NPT Gas Connection3/

Page 77

73Product SpecificationsFront View PRESTIGE Solo 175/250

Page 78 - Product Specifications

2Do not use this appliance if any parthas been under water. Immediately calla qualified service technician to inspectthe appliance and to repla

Page 79

74Product Specifications37.20” [945 mm]24.70” [628 mm]20.40” [516 mm]18.60” [473 mm]13.40” [340 mm]9.25” [235 mm]3.27” [83 mm]1 1/2” NPT Boiler Supply

Page 80

75Product SpecificationsSide View PRESTIGE Solo 60

Page 81

76Product SpecificationsSide View PRESTIGE Solo 175/250

Page 82

77Product Specifications20.80” [529 mm]15.40” [490 mm]14.72” [374 mm]16.10” [409 mm]5.90” [150 mm]1 1/2” NPT Boiler Supply1 1/2” NPT Boiler Return1” G

Page 83

78Product SpecificationsOutputNote 4157,50094.1%95.1%FuelCombustionEfficiencyInputNote 4OutputNote 4Note 5ThermalEfficiencyNet IBRRatingNote 2Shipping

Page 84

79Product SpecificationsGraph 2: Pressure Loss Through Boiler-Grundfos CirculatorPressure Drop Comparison -Grundfos Note: Minimum allowable flow rate

Page 85

80Product SpecificationsGraph 4: Pressure Loss Through Boiler - Grundfos Circulators Note: Minimum allowable flow rate at full input:- 8 gpm SOLO 175-

Page 86

81 Product SpecificationsGraph 6: Pressure Loss Through Boiler - Grundfos Circulators Note: Minimum allowable flow rate at full input:- 19 gpm SOLO 39

Page 87

Additional quality water heating equipment availablefrom Triangle Tube- Exclusive Tank-in-Tank design- Stainless steel construction- Available in 8 si

Page 88 - Member of

Pre-Installation Items3SECTION I - Pre-Installation ItemsCode ComplianceThis product must be installed in accordance tothe following:- All applicable